Study of dielectric strength of medium voltage cables

Antoniou Athina-Konstantina

Simple record


URIhttp://purl.tuc.gr/dl/dias/B4CCAB59-2378-4898-A1A8-9DA20E454948-
Identifierhttps://doi.org/10.26233/heallink.tuc.104049-
Languageen-
Extent111 pagesen
Extent4.174 kilobytesen
ExtentA4 (210x297mm)en
TitleStudy of dielectric strength of medium voltage cablesen
TitleΜελέτη διηλεκτρικής αντοχής καλωδίων μέσης τάσηςel
CreatorAntoniou Athina-Konstantinaen
CreatorΑντωνιου Αθηνα-Κωνσταντιναel
Contributor [Thesis Supervisor]Peppas Georgiosen
Contributor [Thesis Supervisor]Πεππας Γεωργιοςel
Contributor [Committee Member]Gyftakis Konstantinosen
Contributor [Committee Member]Γυφτακης Κωνσταντινοςel
Contributor [Committee Member]Koutroulis Eftychiosen
Contributor [Committee Member]Κουτρουλης Ευτυχιοςel
PublisherΠολυτεχνείο Κρήτηςel
PublisherTechnical University of Creteen
Academic UnitTechnical University of Crete::School of Electrical and Computer Engineeringen
Academic UnitΠολυτεχνείο Κρήτης::Σχολή Ηλεκτρολόγων Μηχανικών και Μηχανικών Υπολογιστώνel
DescriptionStudy of the dielectric strength of medium-voltage cable jackets under impulse voltage stress. This work involves experimental testing on five different cable types featuring various jacket materials such as PVC, HDPE, MDPE, and PPS+HDPE, with the aim of evaluating their performance under 1.2/50 μs lightning impulses. The results are analyzed using statistical methods (GEV distribution), and both breakdown timing and waveform compliance according to IEC 60060-1 are assessed. en
DescriptionΜελέτη της διηλεκτρικής αντοχής περιβλημάτων καλωδίων μέσης τάσης έναντι κρουστικών υπερτάσεων. Η εργασία περιλαμβάνει πειραματικές δοκιμές σε πέντε διαφορετικούς τύπους καλωδίων με διαφορετικά υλικά περιβλήματος, όπως PVC, HDPE, MDPE και PPS+HDPE, με σκοπό την αξιολόγηση της αντοχής τους υπό συνθήκες 1,2/50 μs κρουστικών παλμών. Τα αποτελέσματα αναλύονται με στατιστικές μεθόδους (GEV), ενώ εξετάζεται επίσης ο χρόνος διάσπασης και η μορφή του κύματος βάσει του προτύπου IEC 60060-1.el
Content SummaryCables in medium voltage networks are exposed to two distinct electrical challenges: the continuous stress of normal operation and the abrupt, high-energy surges produced by lightning or switching events. Although the core insulation provides the primary dielectric barrier, the outer jacket frequently proves to be the first point of weakness during such fast transients. This study investigates the jacket’s response to 1,2/50 μs lightning impulses and demonstrates how material formulation, surface condition, and construction details govern breakdown behavior. Impulse testing was conducted on five types of cable with different nominal voltages, varying jacket compounds (PVC, HDPE, MDPE, PPS+HDPE) and geometry, using a single stage impulse voltage generator. Samples were immersed in insulating oil and subjected to gradually increasing impulses. Oscilloscope traces, paired with visual inspection, confirmed breakdown events. Waveform compliance with IEC 60060-1 was verified via measurements and the generator was also simulated using ATP-EMTP. Breakdown voltages were evaluated through GEV analysis, yielding U10, U50, and U90 levels for each cable. Normalized breakdown field strength (kV/mm) was calculated by dividing breakdown voltage by the measured jacket thickness, offering a geometry-independent performance metric. Additionally, breakdown timing was analyzed to understand how and when insulation failure occurs within the impulse window, giving an indication of the tests and samples consistency. The findings offer clearly defined dielectric performance benchmarks for commonly used MV cable jackets and present a reproducible laboratory procedure encompassing sample preparation, waveform validation, and statistical breakdown evaluation. By quantifying impulse withstand limits and clarifying failure patterns under transient conditions, this work contributes to more robust oversheath assessment and supports the development of testing frameworks that better reflect real-world electrical stresses.en
Content SummaryΗ εργασία εξετάζει την ηλεκτρική συμπεριφορά του εξωτερικού περιβλήματος καλωδίων μέσης τάσης κατά την έκθεσή τους σε κρουστικές τάσεις τύπου κεραυνού (1,2/50 μs). Διενεργήθηκαν πειραματικές δοκιμές σε πέντε καλώδια διαφορετικών γεωμετριών και υλικών περιβλήματος, με τη χρήση γεννήτριας κρουστικών τάσεων και εμβάπτιση σε διηλεκτρικό μέσο. Καταγράφηκαν οι τάσεις διάσπασης και αναλύθηκαν με κατανομή GEV ώστε να εξαχθούν οι τιμές U10, U50 και U90. Επίσης, υπολογίστηκε η ηλεκτρική αντοχή kV/mm και μελετήθηκε η χρονική θέση της διάσπασης εντός του παλμού.el
Type of ItemΔιπλωματική Εργασίαel
Type of ItemDiploma Worken
Licensehttp://creativecommons.org/licenses/by/4.0/en
Date of Item2025-07-18-
Date of Publication2025-
SubjectImpulse testingen
SubjectCable jacketen
SubjectDielectric materialsen
SubjectElectrical testingen
SubjectMedium voltageen
SubjectStatistical analysisen
Bibliographic CitationAthina-Konstantina Antoniou, "Study of dielectric strength of medium voltage cables", Diploma Work, School of Electrical and Computer Engineering, Technical University of Crete, Chania, Greece, 2025en
Bibliographic CitationΑθηνά-Κωνσταντίνα Αντωνίου, "Μελέτη διηλεκτρικής αντοχής καλωδίων μέσης τάσης", Διπλωματική Εργασία, Σχολή Ηλεκτρολόγων Μηχανικών και Μηχανικών Υπολογιστών, Πολυτεχνείο Κρήτης, Χανιά, Ελλάς, 2025el